High Capacity Dryers

Standard Features
  1. Inlet temperature gauge
  2. Refrigeration suction pressure gauge
  3. Refrigeration discharge pressure gauge
  4. Status indicator lights
  5. Compressor ON indicator
  6. Standard NEMA 12 Enclosure
  7. Single skid mounted
  8. Air-Water/Glycol heat exchanger
  9. Air-Air Pre-cooler/re-heater (Economizer)
  10. Condenser automatic water regulating valve
  11. Inlet temperature indicator
  12. Outlet temperature indicator
  13. Compressor sequencer (for units with multiple compressors)
  14. Pump sequencer (for units with duplex pumps)
  15. Air inlet pressure gauge
  16. Air outlet pressure gauge
  17. Zero-purge drain system
  18. Pump pressure gauge
  19. Thermal storage temperature gauge
  20. Rotation protection module
  21. High-temperature module
  22. Pump failure indicator
  23. No-flow indicator
  24. Pump starter with overload protection
  25. Compressor starter with overload protection
  26. Outlet pressure indicator
 
Optional Features
  • Duplex pumping mounted on skid
  • Multiplex compressor
  • Air-cooled condenser
  • Remote condenser
  • Compressor sequencer
  • Three-valve by-pass
  • Mounted pre and after-filter
  • Digital dew point monitor
  • NEMA 4, 4x or 7 electrical
 
CRD Series- Cycling Thermal Mass Refrigerated Dryers
 
CRD - Specifications
 
Model
Capacity
in CFM
Comp. HP
AIR In/Out
Conn.
FLG
Max.
Working
Pressure
PSIG
KW
(Full Load)
Run Load
Amps
Standard
Voltage
Dimensions (inches)
Weight
(lbs)
Length
Width
Height
3500-CRD
3,500
2 x 10
6"
150
15
37
460-3-60
130
60
70
3,900
4000-CRD
4,000
2 x 10
6"
150
15
45
460-3-60
130
60
70
4,200
5000-CRD
5,000
2 x 13
8"
150
19
50
460-3-60
130
60
75
6,000
6000-CRD
6,000
30
8"
150
22
50
460-3-60
130
70
75
7,200
7000-CRD
7,000
35
8"
150
26
65
460-3-60
135
80
77
8,600
8000-CRD
8,000
40
10"
150
30
71
460-3-60
140
82
80
9,800
9000-CRD
9,000
50
10"
150
36
80
460-3-60
145
85
80
12,200
10000-CRD
10,000
50
10"
150
38
91
460-3-60
145
85
80
12,500
12000-CRD
12,000
60
12"
150
45
97
460-3-60
160
90
80
13,800
15000-CRD
15,000
2 x 40
12"
150
60
138
460-3-60
180
90
85
17,000
20000-CRD
20,000
2 x 50
14"
150
75
175
460-3-60
200
100
85
21,500
25000-CRD
25,000
120
16"
150
93
186
460-3-60
210
120
87
23,000
30000-CRD
30,000
150
18"
150
112
195
460-3-60
230
125
90
27,000
Capacity rated at Standard CAGI Inlet conditions - Pressure = 100 PSIG, Temperature = 100 Deg. F and Ambient Temperature = 100 Deg. F
 
NRD Series – Non-Cycling Refrigerated Dryers
NRD - Specifications
 
Model
Capacity
in CFM
Comp. HP
In/Out Conn.
Inches
Max.
Working
Pressure
PSIG
Full Load
KW
Full Load
Amps
Standard
Voltage
Dimensions (inches)
Weight
(lbs)
Length
Width
Height
3500-NRD
3,500
2 x 10
6"FLG
150
15
45
460-3-60
130
60
70
3,700
4000-NRD
4,000
2 x 10
6"FLG
150
15
45
460-3-60
130
60
70
4,000
5000-NRD
5,000
2 x 13
8"FLG
150
19
65
460-3-60
130
60
75
4,800
6000-NRD
6,000
30
8"FLG
150
22
50
460-3-60
130
70
75
5,200
7000-NRD
7,000
35
8"FLG
150
26
63
460-3-60
135
80
77
6,500
8000-NRD
8,000
40
10"FLG
150
30
71
460-3-60
140
82
80
7,500
9000-NRD
9,000
50
10"FLG
150
38
69
460-3-60
145
85
80
8,600
10000-NRD
10,000
50
10"FLG
150
38
69
460-3-60
145
85
80
9,700
Capacity rated at Standard CAGI Inlet conditions - Pressure = 100 PSIG, Temp. = 100 Deg. F and Ambient Temp. = 100 Deg. F. All above models are standard air-cooled. For water-cooled units, consult factory. Full load amps at standard voltage.